RDG for DPF Host Trusted with Firefly Time Synchronization, OVN-Kubernetes and HBN Services
Created on Jan 2026 Scope This Reference Deployment Guide (RDG) provides detailed instructions on how to deploy, configure and validate the NVIDIA® DOCA™ Firefly Time Synchronization Service within a Kubernetes cluster using the DOCA Platform Framework (DPF). This document is an extension of the RDG for DPF Host Trusted with OVN-Kubernetes and HBN Services (referred to as the Baseline RDG). It details the additional steps and modifications required to deploy the Firefly Time Sync Service into the environment established by the Baseline RDG.
文档目录
Created on Jan 2026
Scope
This Reference Deployment Guide (RDG) provides detailed instructions on how to deploy, configure and validate the NVIDIA® DOCA™ Firefly Time Synchronization Service within a Kubernetes cluster using the DOCA Platform Framework (DPF). This document is an extension of the RDG for DPF Host Trusted with OVN-Kubernetes and HBN Services (referred to as the Baseline RDG). It details the additional steps and modifications required to deploy the Firefly Time Sync Service into the environment established by the Baseline RDG.
This guide is designed for experienced System Administrators, System Engineers, and Solution Architects seeking to implement high-precision time synchronization in high-performance Kubernetes clusters using NVIDIA BlueField DPU and DPF. Familiarity with the Baseline RDG is required.
Warning
- This reference implementation, as the name implies, is a specific, opinionated deployment example designed to address the use case described above.
- While other approaches may exist to implement similar solutions, this document provides a detailed guide for this particular method.
Abbreviations and Acronyms
| Term | Definition | Term | Definition |
|---|---|---|---|
| BC | Boundary Clock | NTP | Network Time Protocol |
| BFB | BlueField Bootstream | OC | Ordinary Clock |
| BGP | Border Gateway Protocol | OVN | Open Virtual Network |
| CNI | Container Network Interface | PHC | PTP Hardware Clock |
| DOCA | Data Center Infrastructure-on-a-Chip Architecture | PRTC | Primary Reference Time Clock (e.g., ITU-T G.8272) |
| DPF | DOCA Platform Framework | PTP | Precision Time Protocol (IEEE 1588) |
| DPU | Data Processing Unit | RDG | Reference Deployment Guide |
| DTS | DOCA Telemetry Service | RDMA | Remote Direct Memory Access |
| G.8275.1 | ITU-T Recommendation for PTP Profile (Full Timing Support) | SF | Scalable Function |
| GM | Grandmaster Clock | SFC | Service Function Chaining |
| HBN | Host-Based Networking | SR-IOV | Single Root Input/Output Virtualization |
| IPAM | IP Address Management | TAI | International Atomic Time |
| ITU-T | International Telecommunication Union - Telecommunication Standardization Sector | TOR | Top of Rack |
| K8S | Kubernetes | UTC | Coordinated Universal Time |
| MAAS | Metal as a Service |
Introduction
Accurate time synchronization is critical for various modern data center applications, including distributed databases, real-time analytics, precise event ordering, and detailed telemetry. While Network Time Protocol (NTP) is commonly used and provides millisecond-level time accuracy, which is sufficient for many legacy applications, emerging applications—particularly in fields such as artificial intelligence (AI) and high-performance computing—require time synchronization with precision levels far beyond what NTP can offer. These applications often necessitate time accuracy in the range of tens of nanoseconds to microseconds.
The Firefly Time Sync Service, deployed via the NVIDIA DOCA Platform Framework (DPF) , leverages the Precision Time Protocol (PTP) capabilities of NVIDIA BlueField® DPU and NVIDIA Spectrum™ switches to deliver highly accurate time synchronization across the cluster.
Firefly runs the PTP stack directly on the DPU's Arm cores, synchronizing the DPU's PTP Hardware Clock (PHC). It then facilitates the synchronization of the DPU's system clock and the host server's system clock with this precise PHC. This architecture offloads the time synchronization task from the host CPU and provides a robust, OS-agnostic solution. This combined approach enables the full utilization of the DPU for precise timekeeping (sub-microsecond accuracy), supporting time-sensitive applications and enhancing overall data center synchronization.
The guide details the steps required to achieve highly accurate, PTP-based time synchronization across cluster nodes equipped with NVIDIA® BlueField® DPU, interconnected via NVIDIA® Spectrum® switches running Cumulus Linux. Leveraging NVIDIA's DPF, administrators can provision and manage DPU resources while deploying and orchestrating the Firefly Time Sync Service alongside other essential infrastructure components, like accelerated OVN-Kubernetes and Host-Based Networking (HBN).
This document extends the capabilities of the DPF-managed Kubernetes cluster described in the RDG for DPF Host Trusted with OVN-Kubernetes and HBN Services (referred to as the Baseline RDG) by deploying the NVIDIA DOCA Firefly Time Sync Service within the existing DPF deployment (which includes OVN-Kubernetes and HBN services) to achieve a comprehensive, accelerated, and precisely synchronized infrastructure.
References
This section supplements the "References" section of the Baseline RDG. Refer to the Baseline RDG (Section "References") for other relevant references.
- RDG for DPF Host Trusted with OVN-Kubernetes and HBN Services
- NVIDIA DOCA Firefly Service Guide
- NVIDIA DPF GitHub Repository - Firefly 文档
- NVIDIA 5T for 5G User Manual
- ITU-T G.8275.1
- Linux PTP Project
Solution Architecture
The overall solution architecture remains consistent with the Baseline RDG (Section "Solution Architecture"), with the addition of components and configurations for time synchronization using the Firefly Time Sync Service.
Key Components and Technologies
This section highlights the key technologies
involved in the time synchronization solution, supplementing those described in the Baseline RDG (Section "Solution Architecture", Subsection "Key Components and Technologies").
-
Precision Time Protocol (PTP) (defined by IEEE 1588) is a protocol used to synchronize clocks throughout a computer network. It is designed to achieve sub-microsecond accuracy, making it suitable for demanding applications in telecommunications, finance, industrial automation, and high-performance computing clusters. PTP relies on a master-slave hierarchy of clocks and uses hardware timestamping to minimize latency and jitter introduced by network components and software stacks.
-
NVIDIA DOCA™ Firefly Time Sync Service is an NVIDIA DOCA service that enables high-precision time synchronization for NVIDIA BlueField DPU and connected hosts. It leverages the PTP capabilities of the DPU hardware to achieve sub-microsecond accuracy. The Firefly service supports multiple deployment modes, configuration profiles, and third-party providers to deliver time synchronization services to DPU and connected hosts.
Solution Design
Solution Logical Design
The logical design described in the Baseline RDG (Section "Solution Architecture", Subsection "Solution Design", Sub-subsection "Solution Logical Design") is augmented with the PTP Grandmaster node and the time synchronization components.
Additions for Firefly:
- PTP Grandmaster Node is added:
- A bare-metal server equipped with an NVIDIA ConnectX-7 NIC.
- Connected to the high-speed switch (e.g., SN3700).
- The SN3700 switch acts as a PTP Boundary Clock.
- Firefly Time Sync Services are deployed on both K8s tenant hosts and DPU nodes:
- The Firefly Time Sync Service on the DPU acts as a PTP client, synchronizing the PHCs from the SN3700, and then the DPU's Arm system clock.
- The Firefly Time Sync Service on the host synchronizes the host system clock to the DPU's PHC.

K8s Cluster Logical Design
The K8s cluster logical design remains the same as described in the Baseline RDG (Section "Solution Architecture", Subsection "Solution Design", Sub-subsection "K8s Cluster Logical Design").
DPF is responsible for deploying the Firefly DPUServices—both DPU and host components—onto the respective DPU K8s worker nodes and their hosts.
Timing Network Design
This section details the time synchronization architecture.
Key Design Considerations
-
The PTP profile demonstrated utilizes Layer 2 transport. It aligns closely with the ITU-T G.8275.1 telecom profile, which defines PTP for phase/time synchronization with full timing support from the network. This profile maps PTP messages directly over Ethernet using a specific EtherType and employs non-forwardable, link-local multicast MAC addresses (e.g.,
01-80-C2-00-00-0E) for PTP message communication between peer ports. The solution also incorporates Boundary Clock (BC) functionality on the NVIDIA Spectrum switch. -
The PTP time source (Grandmaster) used in this reference setup is a Linux server configured as a PTP Grandmaster for demonstration purposes and may not meet formal PTP Grandmaster clock performance standards (like ITU-T G.8272 PRTC). Setting up the Grandmaster node itself (OS installation, basic configuration) is not be demonstrated in detail; however, its PTP "master" configuration files are provided as examples.
Warning: For a UTC-traceable and accurate reference, a PRTC: ITU-T G.8272-compliant Grandmaster connected to GPS/GNSS can be used.
-
The setup described is a reference deployment and does not encompass all considerations required for a production-grade, highly available, and fully redundant time synchronization infrastructure, such as multiple Grandmaster deployment or complex failover scenarios (except for basic PTP interface redundancy on the Firefly Time Sync Service).
-
NTP Considerations:
- The cluster is expected to be deployed with NTP (Network Time Protocol) initially, as per the Baseline RDG.
- Control-plane nodes will continue to use NTP and are not part of the PTP synchronization domain in this guide.
- NTP service should be disabled on Worker Nodes and DPU once the Firefly Time Sync Service is operational and PTP synchronization is established. This is typically handled by the DPF's DPUFlavor for the DPU and is the user's responsibility for the host.
Core Synchronization Elements
- PTP Grandmaster (GM) Node: A dedicated server (bare-metal recommended) acting as the primary time source for the PTP domain. In this RDG, a Linux server with a ConnectX-7 NIC is configured to function as a PTP Grandmaster. For production environments, a dedicated, commercially available PTP Grandmaster appliance compliant with standards such as ITU-T G.8272 (PRTC-A or PRTC-B) is recommended for higher stability and accuracy.
- NVIDIA Spectrum 交换机 (as PTP Boundary Clocks): The existing Spectrum switches (e.g., SN3700) are configured to act as PTP Boundary Clocks (BCs). They synchronize to an upstream PTP clock (either the GM or another BC) and provide PTP time to downstream devices (DPU or other BCs).
- NVIDIA BlueField-3 DPU (as PTP Ordinary Clock–Slave/Client): The DPU on the worker nodes run the Firefly Time Sync Service. The DPU's PTP client synchronizes its PTP Hardware Clock (PHC) to the PTP time provided by the connected switch (BC).
- DOCA Platform Framework (DPF): As in the Baseline RDG, DPF orchestrates the deployment and lifecycle management of DPUServices, now including the Firefly Time Sync Service components.
PTP Network Hierarchy
- PTP Grandmaster (GM): The authoritative time source for the PTP domain.
- In this RDG: A Linux server with ConnectX-7, configured as a PTP master.
- PTP Boundary Clock (BC): The SN3700 Cumulus Linux switch.
- It synchronizes its clock to the PTP GM (acting as a PTP slave towards the GM).
- It provides PTP time to the DPU (acting as a PTP master towards the DPU).
- PTP Ordinary Clock (OC) - Slave: The BlueField-3 DPU running the Firefly Time Sync Service.
- The DPU's PTP client synchronizes its PHC from the PTP time provided by the switch (BC).
Clock Types and Standards (Targeted)
- PTP Grandmaster (Conceptual): Aims for PRTC-like behavior (ITU-T G.8272).
- Switch (Boundary Clock): Configured to meet ITU-T G.8273.2 Class C T-BC requirements (without SyncE).
- DPU (Ordinary Clock - Slave): Configured to meet ITU-T G.8273.2 Class C T-TSC (Telecom Time Slave Clock) requirements (without SyncE).
Warning: Reference PTP configurations for the DPU (via Firefly DPUServiceConfiguration CR), the Switch (Cumulus Linux commands), and the PTP Grandmaster (linuxptp configuration files) are provided in the relevant subsections of the 'Deployment and Configuration' section of this RDG.
Firefly Time Sync Service Design
- Firefly DPU Service (firefly-dpu-dpuservice). The Firefly DPU service is orchestrated as a DPU Service deployed on the BlueField DPU's Arm cores and is responsible for the primary PTP client operations and DPU time synchronization.
- PTP Service: Utilizes
PTP4Lprogram as a third-party provider for PTP time synching service - OS Time Calibration: Utilizes
PHC2SYSprogram as a third-party provider for OS time calibration service on the DPU Arm OS - Service Interface (Trusted Scalable Function): Utilizes a Trusted Scalable Function (SF) as its network interface to the fabric. This is crucial for achieving the high-precision timestamping functionality required by Firefly. The Trusted SF is configured and provisioned using DPUFlavor and potentially DPUServiceNAD (Network Attachment Definition) DPF Custom Resources.
- Redundant PTP Interfaces: Supports configuration of two service interfaces (Trusted SFs) for PTP link redundancy. This allows the service to maintain PTP lock in case one of the physical links or paths to the PTP Boundary Clock fails.
- PTP Profile Configuration: The PTP client within the Firefly DPU service is configured to align with the ITU-T G.8275.1 telecom profile, utilizing L2 transport and specific PTP message parameters.
- Custom Flows for PTP Control Traffic: DPF facilitates the setup of custom OVS flows to steer the specific PTP control traffic (non-forwardable L2 multicast) between the physical port and the Firefly service's SF. This ensures
- PTP Service: Utilizes
PTP packets are correctly handled and not misrouted.
-
PTP Monitor Server: DPU Firefly service acts as a server exposing PTP monitoring data to a PTP Monitor Client (Firefly Host Monitor Service)
-
Communication with Host Service: Exposes a DPU Cluster NodePort service, which allows the Firefly Host Monitor Service running on the x86 host to communicate with the DPU service for retrieving PTP monitoring information.
-
Firefly Host Monitor Service (firefly-host-monitor-dpuservice). The Firefly Host Monitor service is orchestrated as a DPUService deployed on the X86 tenant cluster hosts and is responsible for PTP state monitoring and host time synchronization.
- OS Time Calibration: Utilizes
PHC2SYSprogram as a third-party provider for OS time calibration service on the Host OS - Network Interface (VF): The service utilizes a Virtual Function (VF) injected into its pod by the OVN-Kubernetes CNI (via Multus and the SRIOV Network Operator). This VF shares the underlying PTP Hardware Clock (PHC) with the DPU, allowing the Firefly Host Monitor service to accurately fetch the DPU's synchronized PHC time.
- PTP Monitor Client: Host Firefly service acts as a client registered for consuming PTP monitoring data from a PTP Monitor Server (Firefly DPU Service)
- Communication with DPU Service: The Firefly DPU service (running on the DPU) exposes a DPU Cluster NodePort Kubernetes service. The Firefly Host Monitor service (running on the host) in turn exposes a tenant cluster Kubernetes service, which facilitates its connection to the local DPU's NodePort service. This communication channel is primarily used to monitor the DPU's PTP synchronization state and verify its health.
- OS Time Calibration: Utilizes

Time Synchronization Flow
- The PTP Grandmaster node generates and distributes PTP timing messages.
- The SN3700 switch (PTP BC) receives these messages on its PTP slave port connected to the GM, synchronizes its internal clock, and regenerates PTP messages on its PTP master ports connected to the DPU.
- The BlueField-3 DPU (running Firefly's PTP client) receives PTP messages from the switch on its PTP slave port(s) and disciplines its PTP Hardware Clock (PHC). Firefly Time Sync Service supports using two DPU ports for PTP slave for link redundancy.
- The Firefly DPU service synchronizes the DPU's Arm OS system clock to its disciplined PTP Hardware Clock (PHC).
- The Firefly Host Monitor service, running on the host, monitors the PTP synchronization state on the DPU.
- The Firefly Host Monitor service then synchronizes the host's OS system clock to the DPU's precise PHC.

Service Function Chaining (SFC) Design
The Firefly Time Sync Service deployment leverages the Service Function Chaining (SFC) capabilities inherent in the DPF system, as described in the Baseline RDG (refer to HBN and OVN-Kubernetes SFC discussions in the Baseline RDG, Section "DPF Installation", Subsection "DPU Provisioning and Service Installation"). However, the introduction of Firefly for PTP traffic necessitates specific considerations and alterations to the traffic flow:
- The deployment of the Firefly Time Sync Service modifies the existing Service Function Chain (SFC). The original SFC, designed for HBN and OVN-Kubernetes services, now takes the form of a branched structure. This "T-shaped" chain allows the Firefly service, residing on a dedicated branch, to directly communicate with the physical network interface for PTP message exchange.
- Concurrently, DPF orchestrates a custom flow mechanism specifically for PTP's non-forwardable L2 multicast traffic (e.g., packets to
01-80-C2-00-00-0E). This mechanism ensures that these specialized PTP packets are handled distinctly from the primary workload data path, being precisely redirected only between the wire and the Firefly service on the DPU. Such isolation prevents the propagation of link-local PTP packets to other services in the chain, thereby maintaining the integrity of both PTP communication and general workload traffic.

Firewall Design
The firewall design remains as described in the Baseline RDG (Section "Solution Architecture", Subsection "Solution Design", Sub-subsection "Firewall Design").
The PTP GM node is connected to both the High-Speed and Management networks, as shown in the diagram with the worker nodes.
PTP traffic for this internal cluster synchronization does not traverse the main firewall providing external connectivity.
Software Stack Components
This section updates the software stack from the Baseline RDG (Section "Solution Architecture", Subsection "Software Stack Components") with Firefly-specific components.

Error: Make sure to use the exact same versions for the software stack as described above and in the Baseline RDG.
Bill of Materials
This section updates the Bill of Materials (BOM) from the Baseline RDG (Section "Solution Architecture", Subsection "Bill of Materials"). All other components remain as per the Baseline RDG.

Deployment and Configuration
This section details the deployment and configuration steps, referencing the Baseline RDG where procedures are unchanged and detailing new or modified steps for Firefly Time Sync Service integration.
Node and Switch Definitions
These are the definitions and parameters used for deploying the demonstrated fabric:
Refer to the "Node and Switch Definitions" in the Baseline RDG (Section "Deployment and Configuration", Subsection "Node and Switch Definitions").
The following provides the definition for the new PTP Grandmaster Node switch port:
| Switch Port Usage | ||
|---|---|---|
| Hostname | Rack ID | Ports |
hs-switch |
1 | swp1,11-14,20 |
mgmt-switch |
1 | swp1-4 |
| Hosts | |||||
|---|---|---|---|---|---|
| Rack | Server Type | Server Name | Switch Port | IP and NICs |
Default Gateway
| Rack | PTP GM Node | Hostname | Switch Ports | IP Addresses | Default Gateway |
|---|---|---|---|---|---|
| Rack1 | PTP GM Node | ptp-gm |
mgmt-switch: swp4hs-switch: swp20 |
eno4: 10.0.110.8/24ens1f1np1: n/a | 10.0.110.254 |
Wiring
Reference the Baseline RDG: (Section "Deployment and Configuration", Subsection "Wiring", including Sub-subsections "Hypervisor Node" and "K8s Worker Node") for Hypervisor and K8s Worker Node wiring.
PTP GM Node
- Basic wiring is similar to that of a Worker Node (with single high-speed port)
- Connect the management interface of the
ptp-gmserver to themgmt-switch(e.g., SN2201). - Connect the ConnectX-7 interface (intended for PTP) of the
ptp-gmserver to thehs-switch(e.g., SN3700). This port on the switch will be a PTP slave port from the switch's perspective, receiving time from the GM.

Fabric Configuration
Updating Cumulus Linux
No change from the Baseline RDG (Section "Deployment and Configuration", Subsection "Fabric Configuration", Sub-subsection "Updating Cumulus Linux"). Ensure switches are in the recommended Cumulus Linux version.
Configuring the Cumulus Linux Switch
This section details modifications to the switch configuration (hs-switch, e.g., SN3700) to enable PTP Boundary Clock functionality. The configuration from the Baseline RDG (Section "Deployment and Configuration", Subsection "Fabric Configuration", Sub-subsection "Configuring the Cumulus Linux Switch") for BGP and basic L3 networking remains foundational. The following are additional configurations for PTP:
nv set service ptp 1 state enabled
nv set service ptp 1 multicast-mac non-forwarding
nv set service ptp 1 current-profile default-itu-8275-1
nv set interface swp20 link state up
nv set interface swp20 type swp
nv set interface 11-14,20 ptp state enabled
nv config apply -y
The SN2201 switch (mgmt-switch) is configured as follows after adding the PTP GM node:
nv set interface swp4 link state up
nv set interface swp4 type swp
nv set interface swp1-4 bridge domain br_default
nv config apply -y
Host Configuration
No change from the Baseline RDG (Section "Deployment and Configuration", Subsection "Host Configuration").
Hypervisor Installation and Configuration
No change from the Baseline RDG (Section "Deployment and Configuration", Subsection "Hypervisor Installation and Configuration").
Prepare Infrastructure Servers
No change from the Baseline RDG (Section "Deployment and Configuration", Subsection "Prepare Infrastructure Servers") regarding Firewall VM, Jump VM, MaaS VM.
Provision Master VMs and Worker Nodes Using MaaS
No change from the Baseline RDG (Section "Deployment and Configuration", Subsection "Provision Master VMs and Worker Nodes Using MaaS").
The PTP Grandmaster node is a separate, manually configured node in this RDG.
PTP GrandMaster Server Configuration
As mentioned before, detailed OS installation and basic server configuration for the Grandmaster node are not covered in this RDG. The GM in this reference deployment is assumed to be a Linux server with the linuxptp package installed, using its ConnectX-7 NIC for PTP.
The following describes the reference ptp4l.conf configuration file used for the PTP Grandmaster node in this RDG. This file should typically be placed at /etc/linuxptp/ptp4l-master.conf on the GM server. In this example, the interface connected to the high-speed switch is "ens1f1np1".
[global]
#
domainNumber 24
serverOnly 1
verbose 1
logging_level 6
dataset_comparison G.8275.x
G.8275.defaultDS.localPriority 128
maxStepsRemoved 255
logAnnounceInterval -3
logSyncInterval -4
logMinDelayReqInterval -4
G.8275.portDS.localPriority 128
clockClass 6
ptp_dst_mac 01:80:C2:00:00:0E
network_transport L2
fault_reset_interval 1
hybrid_e2e 0
[ens1f1np1]
K8s Cluster Deployment and Configuration
Kubespray Deployment and Configuration
The procedures for initial Kubernetes cluster deployment using Kubespray for the master nodes, and subsequent verification, remain unchanged from the Baseline RDG (Section "K8s Cluster Deployment and Configuration", Subsections: "Kubespray Deployment and Configuration", "Deploying Cluster Using Kubespray Ansible Playbook","K8s Deployment Verification".
Warning: As in Baseline RDG, Worker nodes are added later, after DPF and prerequisite components for accelerated CNI are installed
DPF Installation
The DPF installation process (Operator, System components) largely follows the Baseline RDG. The primary modifications occur during "DPU Provisioning and Service Installation" to deploy the Firefly Time Sync Service configurations.
Software Prerequisites and Required Variables
Refer to the Baseline RDG (Section "DPF Installation", Subsection "Software Prerequisites and Required Variables") for software prerequisites (like helm, envsubst) and the required environment variables defined in export_vars.env.
CNI Installation
No change from the Baseline RDG (Section "DPF Installation", Subsection "CNI Installation").
DPF Operator Installation
No change from the Baseline RDG (Section "DPF Installation", Subsection "DPF Operator Installation").
DPF System Installation
No change from the Baseline RDG (Section "DPF Installation", Subsection "DPF System Installation").
Install Components to Enable Accelerated CNI Nodes
No change from the Baseline RDG (Section "DPF Installation", Subsection "Install Components to Enable Accelerated CNI Nodes").
DPU Provisioning and Service Installation
安装
本节详细介绍 Firefly 时间同步服务的部署。该过程涉及为 Firefly 创建专用的自定义资源 (CR),并配置必要的 DPF 对象,以便在 DPU 预配置阶段同时部署该服务。
虽然部署 DPUService(如 OVN、HBN、DTS 和 BlueMan)的通用方法已在基线 RDG(“DPF 安装”部分,“DPU 预配置和服务安装”小节)中介绍,但本节专门介绍如何将 Firefly 服务与 OVN 和 HBN 核心服务一起部署。
-
在部署
manifests/05-dpudeployment-installation目录下的对象之前,需要按照基线 RDG 的说明进行一些调整,以包含 Firefly 服务并获得更好的性能结果。-
使用以下 YAML 创建一个新的 DPUFlavor:
警告:
- 根据基线 RDG:在提供的示例中,参数
NUM_VF_MSIX设置为 48,这适用于本 RDG 中使用的 HP 服务器。请将此参数设置为 NIC 所在 NUMA 节点 的 物理核心数。 - 使用特殊注解来创建 Firefly 所需的 Trusted SF。
- 通过参数
REAL_TIME_CLOCK_ENABLE启用 Firefly 所需的实时时钟。 - 在 DPU 上禁用 NTP 服务,因为 Firefly 运行
phc2sys时需要。
--- apiVersion: provisioning.dpu.nvidia.com/v1alpha1 kind: DPUFlavor metadata: annotations: provisioning.dpu.nvidia.com/num-of-trusted-sfs: "2" name: dpf-provisioning-hbn-ovn-performance-firefly namespace: dpf-operator-system spec: bfcfgParameters: - UPDATE_ATF_UEFI=yes - UPDATE_DPU_OS=yes - WITH_NIC_FW_UPDATE=yes configFiles: - operation: override path: /etc/mellanox/mlnx-bf.conf permissions: "0644" raw: | ALLOW_SHARED_RQ="no" IPSEC_FULL_OFFLOAD="no" ENABLE_ESWITCH_MULTIPORT="yes" - operation: override path: /etc/mellanox/mlnx-ovs.conf permissions: "0644" raw: | CREATE_OVS_BRIDGES="no" OVS_DOCA="yes" - operation: override path: /etc/mellanox/mlnx-sf.conf permissions: "0644" raw: "" dpuMode: dpu grub: kernelParameters: - console=hvc0 - console=ttyAMA0 - earlycon=pl011,0x13010000 - fixrttc - net.ifnames=0 - biosdevname=0 - iommu.passthrough=1 - cgroup_no_v1=net_prio,net_cls - hugepagesz=2048kB - hugepages=8072 nvconfig: - device: '*' parameters: - PF_BAR2_ENABLE=0 - PER_PF_NUM_SF=1 - PF_TOTAL_SF=20 - PF_SF_BAR_SIZE=10 - NUM_PF_MSIX_VALID=0 - PF_NUM_PF_MSIX_VALID=1 - PF_NUM_PF_MSIX=228 - INTERNAL_CPU_MODEL=1 - INTERNAL_CPU_OFFLOAD_ENGINE=0 - SRIOV_EN=1 - NUM_OF_VFS=46 - LAG_RESOURCE_ALLOCATION=1 - NUM_VF_MSIX=48 - REAL_TIME_CLOCK_ENABLE=1 ovs: rawConfigScript: | _ovs-vsctl() { ovs-vsctl --no-wait --timeout 15 "$@" } _ovs-vsctl set Open_vSwitch . other_config:doca-init=true _ovs-vsctl set Open_vSwitch . other_config:dpdk-max-memzones=50000 _ovs-vsctl set Open_vSwitch . other_config:hw-offload=true _ovs-vsctl set Open_vSwitch . other_config:pmd-quiet-idle=true _ovs-vsctl set Open_vSwitch . other_config:max-idle=20000 _ovs-vsctl set Open_vSwitch . other_config:max-revalidator=5000 _ovs-vsctl set Open_vSwitch . other_config:ctl-pipe-size=1024 _ovs-vsctl --if-exists del-br ovsbr1 _ovs-vsctl --if-exists del-br ovsbr2 _ovs-vsctl --may-exist add-br br-sfc _ovs-vsctl set bridge br-sfc datapath_type=netdev _ovs-vsctl set bridge br-sfc fail_mode=secure _ovs-vsctl --may-exist add-br br-hbn _ovs-vsctl set bridge br-hbn datapath_type=netdev _ovs-vsctl set bridge br-hbn fail_mode=secure _ovs-vsctl --may-exist add-port br-sfc p0 _ovs-vsctl set Interface p0 type=dpdk _ovs-vsctl set Interface p0 mtu_request=9216 _ovs-vsctl set Port p0 external_ids:dpf-type=physical _ovs-vsctl set Open_vSwitch . external-ids:ovn-bridge-datapath-type=netdev _ovs-vsctl --may-exist add-br br-ovn _ovs-vsctl set bridge br-ovn datapath_type=netdev _ovs-vsctl br-set-external-id br-ovn bridge-id br-ovn _ovs-vsctl br-set-external-id br-ovn bridge-uplink puplinkbrovntobrsfc _ovs-vsctl --may-exist add-port br-ovn pf0hpf _ovs-vsctl set Interface pf0hpf type=dpdk _ovs-vsctl set Interface pf0hpf mtu_request=9216 _ovs-vsctl --may-exist add-port br-sfc p1 _ovs-vsctl set Interface p1 type=dpdk _ovs-vsctl set Interface p1 mtu_request=9216 _ovs-vsctl set Port p1 external_ids:dpf-type=physical _ovs-vsctl set Interface br-ovn mtu_request=9216 cat <<EOT > /etc/netplan/99-dpf-comm-ch.yaml network: renderer: networkd version: 2 ethernets: pf0vf0: mtu: 9000 dhcp4: no bridges: br-comm-ch: dhcp4: yes interfaces: - pf0vf0 EOT # When running Firefly with phc2sys on the DPU, NTP must be disabled hwclock --systohc systemctl disable ntpsec --now - 根据基线 RDG:在提供的示例中,参数
-
调整
dpudeployment.yaml,使其引用适用于性能/Firefly 的 DPUFlavor(该组件在工作节点上预配置 DPU,并定义一组 DPUService 和 DPUServiceChain 在这些 DPU 上运行。DTS 和 BlueMan 服务已被移除):--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUDeployment metadata: name: ovn-hbn-firefly namespace: dpf-operator-system spec: dpus: bfb: bf-bundle flavor: dpf-provisioning-hbn-ovn-performance-firefly dpuSets: - nameSuffix: "dpuset1" nodeSelector: matchLabels: feature.node.kubernetes.io/dpu-enabled: "true" services: ovn: serviceTemplate: ovn serviceConfiguration: ovn hbn: serviceTemplate: hbn serviceConfiguration: hbn firefly-dpu: serviceConfiguration: firefly-dpu serviceTemplate: firefly-dpu firefly-host: serviceConfiguration: firefly-host serviceTemplate: firefly-host dependsOn: - name: firefly-dpu serviceChains: switches: - ports: - serviceInterface: matchLabels: uplink: p0 - service: name: hbn interface: p0_if - service: interface: firefly_if name: firefly-dpu - ports: - serviceInterface: matchLabels: uplink: p1 - service: name: hbn interface: p1_if - service: interface: firefly2_if name: firefly-dpu - ports: - serviceInterface: matchLabels: port: ovn - service: name: hbn interface: pf2dpu2_if -
将 OVN DPUServiceConfig 的
mtu设置为8940(以便在 DPU 上部署 OVN Kubernetes 工作负载时使用与主机相同的 MTU):--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceConfiguration metadata: name: ovn namespace: dpf-operator-system spec: deploymentServiceName: "ovn" serviceConfiguration: helmChart: values: k8sAPIServer: https://$TARGETCLUSTER_API_SERVER_HOST:$TARGETCLUSTER_API_SERVER_PORT podNetwork: $POD_CIDR/24 serviceNetwork: $SERVICE_CIDR mtu: 8940 dpuManifests: kubernetesSecretName: "ovn-dpu" # user needs to populate based on DPUServiceCredentialRequest vtepCIDR: "10.0.120.0/22" # user needs to populate based on DPUServiceIPAM hostCIDR: $TARGETCLUSTER_NODE_CIDR # user needs to populate ipamPool: "pool1" # user needs to populate based on DPUServiceIPAM ipamPoolType: "cidrpool" # user needs to populate based on DPUServiceIPAM ipamVTEPIPIndex: 0 ipamPFIPIndex: 1 -
创建一个新的 DPUServiceNAD,以允许 Firefly 使用具有 Trusted SF 资源且无 IPAM 的网络:
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceNAD metadata: name: mybrsfc-firefly namespace: dpf-operator-system annotations: dpuservicenad.svc.dpu.nvidia.com/use-trusted-sfs: "" spec: resourceType: sf ipam: false bridge: "br-sfc" serviceMTU: 1500 -
为 Firefly DPU 服务创建一个新的 DPUServiceConfig(引用 firefly DPUServiceNAD 网络)和 DPUServiceTemplate:
-
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceConfiguration metadata: name: firefly-dpu namespace: dpf-operator-system spec: deploymentServiceName: firefly-dpu interfaces: - name: firefly_if network: mybrsfc-firefly - name: firefly2_if network: mybrsfc-firefly serviceConfiguration: configPorts: ports: - name: monitor port: 25600 protocol: TCP serviceType: ClusterIP serviceDaemonSet: labels: svc.dpu.nvidia.com/custom-flows: firefly helmChart: values: exposedPorts: ports: monitor: true ptpConfig: ptp.conf ptpInterfaces: firefly_if config: content: ptp.conf: | [global] domainNumber 24 clientOnly 1 verbose 1 logging_level 6 dataset_comparison G.8275.x G.8275.defaultDS.localPriority 128 maxStepsRemoved 255 logAnnounceInterval -3 logSyncInterval -4 logMinDelayReqInterval -4
-
-
G.8275.portDS.localPriority 128 ptp_dst_mac 01:80:C2:00:00:0E network_transport L2 fault_reset_interval 1 hybrid_e2e 0
[firefly_if]
[firefly2_if]
-
为 Firefly DPU 服务创建新的 DPUServiceConfig 和 DPUServiceTemplate:
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceConfiguration metadata: name: firefly-dpu namespace: dpf-operator-system spec: deploymentServiceName: firefly-dpu upgradePolicy: applyNodeEffect: false serviceConfiguration: deployInCluster: true helmChart: values: config: ptp4lArgs: -f /configs/ptp4l.cfg -i firefly_if -i firefly2_if phc2sysArgs: -a -r -l 6 enableTXPortTimestampOffloading: true hostNetwork: false monitorState: 0.0.0.0--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceTemplate metadata: name: firefly-dpu namespace: dpf-operator-system spec: deploymentServiceName: firefly-dpu helmChart: source: chart: doca-firefly repoURL: $HELM_REGISTRY_REPO_URL version: 1.1.9 values: config: isLocalPath: false containerImage: nvcr.io/nvidia/doca/doca_firefly:1.7.4-doca3.2.0 enableTXPortTimestampOffloading: true hostNetwork: false monitorState: 0.0.0.0 phc2sysArgs: -a -r -l 6 resourceRequirements: memory: 512Mi -
为 Firefly Host Monitor 服务创建新的 DPUServiceConfig 和 DPUServiceTemplate:
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceConfiguration metadata: name: firefly-host namespace: dpf-operator-system spec: deploymentServiceName: firefly-host upgradePolicy: applyNodeEffect: false serviceConfiguration: deployInCluster: true helmChart: values: monitorState: '{{ (index .Services "firefly-dpu").Name }}.{{ (index .Services "firefly-dpu").Namespace }}'--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceTemplate metadata: name: firefly-host namespace: dpf-operator-system spec: deploymentServiceName: firefly-host helmChart: source: chart: doca-firefly repoURL: $HELM_REGISTRY_REPO_URL version: 1.1.9 values: containerImage: nvcr.io/nvidia/doca/doca_firefly:1.7.4-doca3.2.0-host hostNetwork: false monitorClientPhc2sysInterface: eth0 monitorClientType: phc2sys phc2sysState: disable ppsDevice: disable ppsState: do_nothing ptpState: disable tolerations: - effect: NoSchedule key: k8s.ovn.org/network-unavailable operator: Exists resourceRequirements: memory: 512Mi -
其余配置文件保持不变,包括:
-
BFB 用于将 BlueField Bitstream 下载到共享卷。
--- apiVersion: provisioning.dpu.nvidia.com/v1alpha1 kind: BFB metadata: name: bf-bundle namespace: dpf-operator-system spec: url: $BLUEFIELD_BITSTREAM -
OVN DPUServiceTemplate 用于将 OVN Kubernetes 工作负载部署到 DPU。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceTemplate metadata: name: ovn namespace: dpf-operator-system spec: deploymentServiceName: "ovn" helmChart: source: repoURL: $OVN_KUBERNETES_REPO_URL chart: ovn-kubernetes-chart version: $TAG values: commonManifests: enabled: true dpuManifests: enabled: true leaseNamespace: "ovn-kubernetes" gatewayOpts: "--gateway-interface=br-ovn" -
HBN DPUServiceConfig 和 DPUServiceTemplate 用于将 HBN 工作负载部署到 DPU。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceConfiguration metadata: name: hbn namespace: dpf-operator-system spec: deploymentServiceName: "hbn" serviceConfiguration: serviceDaemonSet: annotations: k8s.v1.cni.cncf.io/networks: |- [ {"name": "iprequest", "interface": "ip_lo", "cni-args": {"poolNames": ["loopback"], "poolType": "cidrpool"}}, {"name": "iprequest", "interface": "ip_pf2dpu2", "cni-args": {"poolNames": ["pool1"], "poolType": "cidrpool", "allocateDefaultGateway": true}} ] helmChart: values: configuration: perDPUValuesYAML: | - hostnamePattern: "*" values: bgp_peer_group: hbn startupYAMLJ2: | - header: model: BLUEFIELD nvue-api-version: nvue_v1 rev-id: 1.0 version: HBN 2.4.0 - set: interface: lo: ip: address: {{ ipaddresses.ip_lo.ip }}/32: {} type: loopback p0_if,p1_if: type: swp link: mtu: 9000 pf2dpu2_if: ip: address: {{ ipaddresses.ip_pf2dpu2.cidr }}: {} type: swp link: mtu: 9000 router: bgp: autonomous-system: {{ ( ipaddresses.ip_lo.ip.split(".")[3] | int ) + 65101 }} enable: on graceful-restart: mode: full router-id: {{ ipaddresses.ip_lo.ip }} vrf: default: router: bgp: address-family: ipv4-unicast: enable: on redistribute: connected: enable: on ipv6-unicast: enable: on redistribute: connected: enable: on enable: on neighbor: p0_if: peer-group: {{ config.bgp_peer_group }} type: unnumbered p1_if: peer-group: {{ config.bgp_peer_group }} type: unnumbered path-selection: multipath: aspath-ignore: on peer-group: {{ config.bgp_peer_group }}: remote-as: external interfaces: ## NOTE: Interfaces inside the HBN pod must have the `_if` suffix due to a naming convention in HBN. - name: p0_if network: mybrhbn - name: p1_if network: mybrhbn - name: pf2dpu2_if network: mybrhbn--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceTemplate metadata: name: hbn namespace: dpf-operator-system spec: deploymentServiceName: "hbn" helmChart: source: repoURL: $HELM_REGISTRY_REPO_URL version: 1.0.5 chart: doca-hbn values: image: repository: $HBN_NGC_IMAGE_URL tag: 3.2.1-doca3.2.1 resources: memory: 6Gi nvidia.com/bf_sf: 3 -
OVN DPUServiceCredentialRequest 用于允许跨集群通信。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceCredentialRequest metadata: name: ovn-dpu namespace: dpf-operator-system spec: serviceAccount: name: ovn-dpu namespace: dpf-operator-system duration: 24h type: tokenFile secret: name: ovn-dpu namespace: dpf-operator-system metadata: labels: dpu.nvidia.com/image-pull-secret: "" -
DPUServiceInterfaces 用于 DPU 上的物理端口。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceInterface metadata: name: p0 namespace: dpf-operator-system spec: template: spec: template: metadata: labels: uplink: "p0" spec: interfaceType: physical physical: interfaceName: p0 --- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceInterface metadata: name: p1 namespace: dpf-operator-system spec: template: spec: template: metadata: labels: uplink: "p1" spec: interfaceType: physical physical: interfaceName: p1 -
OVN DPUServiceInterface 用于定义连接到 DPU 上 OVN 工作负载的端口。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceInterface metadata: name: ovn namespace: dpf-operator-system spec: template: spec: template: metadata: labels: port: ovn spec: interfaceType: ovn -
DPUServiceIPAM 用于在 DPUCluster 上设置 IP 地址管理。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceIPAM metadata: name: ... namespace: dpf-operator-system spec: ...
-
部署DPUService
-
为HBN中的环回接口创建DPUServiceIPAM。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceIPAM metadata: name: pool1 namespace: dpf-operator-system spec: ipv4Network: network: "10.0.120.0/22" gatewayIndex: 3 prefixSize: 29 -
为HBN中的环回接口创建DPUServiceIPAM。
--- apiVersion: svc.dpu.nvidia.com/v1alpha1 kind: DPUServiceIPAM metadata: name: loopback namespace: dpf-operator-system spec: ipv4Network: network: "11.0.0.0/24" prefixSize: 32 -
使用以下命令应用上述所有YAML文件:
跳板机控制台
$ cat manifests/05-dpudeployment-installation/*.yaml | envsubst | kubectl apply -f - -
验证DPUService安装,确保DPUService已创建并已协调,DPUServiceIPAM已协调,DPUServiceInterface已协调,以及DPUServiceChain已协调:
注意:这些验证命令可能需要多次运行以确保满足条件。
跳板机控制台
$ kubectl wait --for=condition=ApplicationsReconciled --namespace dpf-operator-system dpuservices -l svc.dpu.nvidia.com/owned-by-dpudeployment=dpf-operator-system_ovn-hbn-firefly dpuservice.svc.dpu.nvidia.com/firefly-dpu-4v26p condition met dpuservice.svc.dpu.nvidia.com/firefly-host-d5c97 condition met dpuservice.svc.dpu.nvidia.com/hbn-77jcn condition met dpuservice.svc.dpu.nvidia.com/ovn-6xnbh condition met $ kubectl wait --for=condition=DPUIPAMObjectReconciled --namespace dpf-operator-system dpuserviceipam --all dpuserviceipam.svc.dpu.nvidia.com/loopback condition met dpuserviceipam.svc.dpu.nvidia.com/pool1 condition met $ kubectl wait --for=condition=ServiceInterfaceSetReconciled --namespace dpf-operator-system dpuserviceinterface --all dpuserviceinterface.svc.dpu.nvidia.com/firefly-dpu-firefly-if-v8r7j condition met dpuserviceinterface.svc.dpu.nvidia.com/firefly-dpu-firefly2-if-h6hhd condition met dpuserviceinterface.svc.dpu.nvidia.com/hbn-p0-if-6jprb condition met dpuserviceinterface.svc.dpu.nvidia.com/hbn-p1-if-fh2w6 condition met dpuserviceinterface.svc.dpu.nvidia.com/hbn-pf2dpu2-if-wks6w condition met dpuserviceinterface.svc.dpu.nvidia.com/ovn condition met dpuserviceinterface.svc.dpu.nvidia.com/p0 condition met dpuserviceinterface.svc.dpu.nvidia.com/p1 condition met $ kubectl wait --for=condition=ServiceChainSetReconciled --namespace dpf-operator-system dpuservicechain --all dpuservicechain.svc.dpu.nvidia.com/ovn-hbn-firefly-d7vtb condition met
K8s集群扩展
向集群添加工作节点
向集群添加工作节点的步骤与基线RDG(“K8s集群扩展”部分,“向集群添加工作节点”小节)保持不变。
- 参考基线RDG:“K8s集群扩展”部分,“向集群添加工作节点”小节。
- 添加新工作节点时,DPF将配置其DPU,并将所有已配置的DPUService(包括新添加的Firefly DPU和主机监控服务)部署到这些节点/DPU上。
注意:部署Firefly主机服务后,请确保在工作节点上禁用NTP。
恭喜——DPF系统已成功安装!
验证
本节详细说明如何验证整体部署。通用DPF系统验证(DPU就绪状态、核心组件如Multus、SR-IOV、OVN在主机/DPU上的DaemonSet状态)与基线RDG(“验证”部分)保持一致。
基础设施延迟和带宽验证
与基线RDG(“验证”部分,“基础设施延迟和带宽验证”小节)相比无变化。本RDG不包括除时间同步之外的新性能测试或验证。
时间同步服务验证
从租户K8s主机监控PTP状态
Firefly主机监控服务应提供日志或状态,指示其监控的DPU的PTP同步状态。
-
验证每个主机上运行一个Firefly Pod,并获取其名称:
跳板机控制台
$ kubectl get pod -n dpf-operator-system -o wide | grep firefly doca-firefly-dgnmf 1/1 Running 1 (2m33s ago) 2m40s 10.233.68.22 worker1 <none> <none> doca-firefly-pkxsm 1/1 Running 1 (2m33s ago) 2m40s 10.233.67.12 worker2 <none> <none> -
查看特定Pod的日志:
跳板机控制台
$ kubectl logs -n dpf-operator-system doca-firefly-dgnmf -
在日志中,查找类似以下示例的输出,指示PTP和主机同步状态。需要关注的关键字段包括:
- gmIdentity:当前Grandmaster时钟的身份。
- port_state:当同步时,DPU的PTP端口应显示
Active。 - master_offset:显示与主时钟的平均、最大和均方根偏移(纳秒)。较低且稳定的值是理想的。
- ptp_stable:当PTP同步稳定时,应显示
Yes或Recovered。 - ptp_time (TAI) 和 system_time (UTC)(在DPU信息下):应反映当前PHC时间和DPU系统时间。
- ptp_ports:列出DPU的PTP端口状态(例如,如果配置了冗余端口,一个为
Slave,另一个为Listening)。
-
PTP监控日志示例:
PTP监控日志
gmIdentity: B8:3F:D2:FF:FE:6A:E7:67 (b83fd2.fffe.6ae767) portIdentity: 46:66:06:FF:FE:AA:AF:B2 (466606.fffe.aaafb2-1) port_state: Active domainNumber: 24 master_offset: avg: 7 max: 19 rms: 5 gmPresent: true ptp_stable: Yes UtcOffset: 37 timeTraceable: 0 frequencyTraceable: 0 grandmasterPriority1: 128 gmClockClass: 6 gmClockAccuracy: 0xfe grandmasterPriority2: 128 gmOffsetScaledLogVariance: 0xffff ptp_time (TAI): Thu Jan 15 07:15:33 2026 ptp_time (UTC adjusted): Thu Jan 15 07:14:56 2026 system_time (UTC): Thu Jan 15 07:14:56 2026 ptp_ports: 46:66:06:FF:FE:AA:AF:B2 (466606.fffe.aaafb2-1) - Slave 46:66:06:FF:FE:AA:AF:B2 (466606.fffe.aaafb2-2) - Listening Host information: system_time (UTC): Thu Jan 15 07:14:56 2026 phc_time (TAI): Thu Jan 15 07:15:33 2026 -
有关更多PTP监控信息,请参阅DOCA Firefly服务指南(参考文献列表)。
自动主机系统时钟同步验证
注意:部署Firefly主机服务后,请确保在工作节点上禁用NTP。
如本RDG所述,Firefly主机监控服务还负责将主机操作系统系统时钟同步到PHC,并使用PHC2SYS程序作为第三方操作系统时间校准提供程序。
-
连接到其中一个租户K8s工作节点主机,并验证NTP服务处于非活动/禁用状态。
-
检查服务在主机文件系统上创建的以下日志:
工作主机控制台
worker1:~# tail -f /var/log/doca/firefly/monitor_client_phc2sys.log phc2sys[1112425.357]: CLOCK_REALTIME phc offset 14 s2 freq +8045 delay 521 phc2sys[1112426.357]: CLOCK_REALTIME phc offset 1 s2 freq +8036 delay 498 phc2sys[1112427.357]: CLOCK_REALTIME phc offset 19 s2 freq +8055 delay 513 phc2sys[1112428.357]: CLOCK_REALTIME phc offset -9 s2 freq +8032 delay 520 phc2sys[1112429.358]: CLOCK_REALTIME phc offset -7 s2 freq +8032 delay 521 phc2sys[1112430.358]: CLOCK_REALTIME phc offset -7 s2 freq +8032 delay 521
offset -11 s2 freq +8025 delay 511 phc2sys[1112431.358]: CLOCK_REALTIME phc offset -9 s2 freq +8024 delay 520 phc2sys[1112432.358]: CLOCK_REALTIME phc offset -11 s2 freq +8019 delay 520 phc2sys[1112433.359]: CLOCK_REALTIME phc offset 4 s2 freq +8031 delay 523 phc2sys[1112434.378]: CLOCK_REALTIME phc offset 3 s2 freq +8031 delay 520 phc2sys[1112435.379]: CLOCK_REALTIME phc offset -13 s2 freq +8016 delay 521
- The log should be actively updating, indicating that `PHC2SYS` is running and periodically comparing and adjusting the host's `CLOCK_REALTIME` (system clock) against the DPU's PHC.
- Stable frequency/delay values and consistently small offset values are good indicators for close and stable synchronization between the host clock and the DPU PHC.
The Monitoring information presented by the Firefly Host Monitor service also provides indications of the host's current system time under the "Host information" section.
- PTP Monitor log example–DPU information:
**PTP Monitor Logs**
ptp_time (TAI): Thu Jan 15 07:15:33 2026 ptp_time (UTC adjusted): Thu Jan 15 07:14:56 2026 system_time (UTC): Thu Jan 15 07:14:56 2026
- PTP Monitor log example–Host information:
**PTP Monitor Logs**
Host information: system_time (UTC): Thu Jan 15 07:14:56 2026 phc_time (TAI): Thu Jan 15 07:15:33 2026
- Host information:
- **phc_time (TAI):** Current PHC time detected by Firefly host service, should match the PHC time presented by DPU (ptp_time TAI)
- **system_time (UTC):** Host's system clock, should be synchronized to the DPU's PHC, after accounting for the UTC offset (e.g., 37 seconds for TAI to UTC). These times should be very closely aligned. Host system time (UTC) should match the DPU's system_time (UTC) as both services are using `PHC2SYS` to sync the system time to a shared PHC.
- Issue "date" command on the host to verify the current system time matches the one shown in the PTP Monitor log. You can compare it to a known accurate time source (e.g., the PTP GM's system clock). The drift should be minimal and within expected PTP accuracy.
**Worker Host Console**
worker1:~# date --iso-8601=ns 2026-01-15T07:18:32,915864585+00:00
### Link Failure/Recovery (PTP Failover on DPU)
The Firefly Host-monitor service should provide logs or status indicating the PTP synchronization state of the DPU it's monitoring information.
- Simulate Link Failure–Administratively bring down the link for the active PTP port on one of the DPU from the switch side.
**SN3700 Switch Console**
nv set interface swp11 link state down nv config apply -y
- Observe failover via PTP Monitor logs on the relevant worker host—look for "State Recovered", an increased error count, and the second port acquiring the "Slave" role.
**PTP Monitor Logs**
gmIdentity: B8:3F:D2:FF:FE:6A:E7:67 (b83fd2.fffe.6ae767) portIdentity: F2:77:76:FF:FE:1A:BE:19 (f27776.fffe.1abe19-2) port_state: Active domainNumber: 24 master_offset: avg: 47 max: 151 rms: 54 gmPresent: true ptp_stable: Recovered UtcOffset: 37 timeTraceable: 0 frequencyTraceable: 0 grandmasterPriority1: 128 gmClockClass: 6 gmClockAccuracy: 0xfe grandmasterPriority2: 128 gmOffsetScaledLogVariance: 0xffff ptp_time (TAI): Tue May 27 15:02:10 2025 ptp_time (UTC adjusted): Tue May 27 15:01:33 2025 system_time (UTC): Tue May 27 15:01:33 2025 ptp_ports: F2:77:76:FF:FE:1A:BE:19 (f27776.fffe.1abe19-1) - Listening F2:77:76:FF:FE:1A:BE:19 (f27776.fffe.1abe19-2) - Slave error_count: 1 last_err_time (UTC): Tue May 27 15:01:04 2025
Host information: system_time (UTC): Tue May 27 15:01:33 2025 phc_time (TAI): Tue May 27 15:02:10 2025
- Simulate Link Recovery–Administratively bring down the network link for the active PTP port on the switch.
**SN3700 Switch Console**
nv set interface swp11 link state up nv config apply -y
- Observe Recovery via PTP Monitor logs–look for "State Recovered", an increased error count, and the first port reacquiring the "Slave" role.
**PTP Monitor Logs**
gmIdentity: B8:3F:D2:FF:FE:6A:E7:67 (b83fd2.fffe.6ae767) portIdentity: F2:77:76:FF:FE:1A:BE:19 (f27776.fffe.1abe19-1) port_state: Active domainNumber: 24 master_offset: avg: 0 max: 11 rms: 5 gmPresent: true ptp_stable: Recovered UtcOffset: 37 timeTraceable: 0 frequencyTraceable: 0 grandmasterPriority1: 128 gmClockClass: 6 gmClockAccuracy: 0xfe grandmasterPriority2: 128 gmOffsetScaledLogVariance: 0xffff ptp_time (TAI): Tue May 27 15:04:39 2025 ptp_time (UTC adjusted): Tue May 27 15:04:02 2025 system_time (UTC): Tue May 27 15:04:02 2025 ptp_ports: F2:77:76:FF:FE:1A:BE:19 (f27776.fffe.1abe19-1) - Slave F2:77:76:FF:FE:1A:BE:19 (f27776.fffe.1abe19-2) - Listening error_count: 2 last_err_time (UTC): Tue May 27 15:03:52 2025
Host information: system_time (UTC): Tue May 27 15:04:02 2025 phc_time (TAI): Tue May 27 15:04:39 2025
## Authors
| | |
|---|---|
|  | **Itai Levy**<br><br>Over the past few years, Itai Levy has worked as a 解决方案 Architect and member of the NVIDIA Networking “解决方案 Labs” team. Itai designs and executes cutting-edge solutions around Cloud Computing, Software-Defined Networking, Storage and Security. His main areas of expertise include NVIDIA BlueField Data Processing Unit (DPU) solutions and accelerated K8s/OpenStack platforms. |